Medium-voltage switchgear is an essential part of industrial and utility power distribution systems. It is used to control, protect, isolate, and monitor electrical circuits between incoming power sources, transformers, motors, and downstream equipment.
Selecting medium-voltage switchgear (MV switchgear) requires more than choosing a voltage level. Rated current, short-circuit capability, insulation level, protection requirements, installation environment, service continuity, and applicable standards all affect the final configuration.
This guide explains the main technical parameters that should be confirmed before selecting MV switchgear or requesting a quotation.
What Is Medium-Voltage Switchgear?
MV switchgear is an assembly of switching, protection, measurement, control, and isolation devices used in electrical distribution systems.
A typical lineup may include circuit breakers, load-break switches, earthing switches, CTs, VTs, protection relays, meters, busbars, and cable compartments.

A typical power path is:
Utility Supply → MV Switchgear → Transformer → LV Switchgear → Loads
When a fault occurs, the protection system detects the abnormal condition and isolates the affected circuit.
Key Parameters for MV Switchgear Selection
System Voltage and Insulation Level
The rated voltage of the switchgear must be suitable for the electrical system and its highest operating voltage.
The rated insulation level should also be confirmed, including power-frequency withstand voltage and lightning-impulse withstand voltage.
Altitude, overvoltage conditions, insulation coordination, and local utility requirements may affect the required insulation level.
Rated Current and Busbar Capacity
The rated continuous current determines how much current the switchgear can carry under specified operating conditions.
For a balanced three-phase system:
I = S ÷ (√3 × V)
where:
- I= current in A
- S= apparent power in kVA
- V= line-to-line voltage in kV
If active power is known:
I = P ÷ (√3 × V × PF)
where P is in kW and V is in kV.
For a single-phase system:
I = S ÷ V
The specification should distinguish between the main busbar current and the current ratings of individual feeders or branch conductors.
Busbar selection should also consider short-circuit strength, temperature rise, conductor material, insulation, and joint design.
Short-Circuit Ratings
Short-circuit capability is one of the most important switchgear parameters.
Three ratings should be distinguished:
Rated short-time withstand current is the RMS current the switchgear can withstand for a specified duration, such as:
25 kA / 3 s
The duration should be based on the short-circuit study and protection clearing time.
Rated peak withstand current defines the maximum instantaneous fault-current peak the equipment can withstand mechanically. In many IEC applications, it is approximately 2.5 times the short-time withstand current at 50 Hz or 2.6 times at 60 Hz, unless the applicable standard or project specifies otherwise.
Rated short-circuit breaking current applies to the circuit breaker and defines the fault current it can safely interrupt.

These values must come from the system short-circuit calculation rather than normal load current.
Circuit Breaker or Load-Break Switch?
A circuit breaker is generally used where automatic fault interruption and relay-based protection are required.

A load-break switch is intended for switching normal load current. In some secondary distribution systems, it may be combined with fuses for transformer protection.
The correct choice depends on the circuit function, fault level, protection philosophy, transformer or load characteristics, and project requirements.
AIS vs. GIS
Another important decision is whether to use air-insulated switchgear (AIS) or gas-insulated switchgear (GIS).
| Item | AIS | GIS |
| Insulation | Air | Sealed gas or gas mixture |
| Space requirement | Generally larger | More compact |
| Initial cost | Generally lower | Generally higher |
| Maintenance access | Usually easier | More specialized |
| Environmental exposure | More exposed to dust and pollution | Primary parts are more isolated |
| SF₆ | Normally not required as main insulation | Traditional designs may use SF₆; SF₆-free technologies are increasingly available |
| Typical use | Industrial plants and conventional substations | Space-limited or demanding environments |
Selection should consider space, maintenance strategy, environmental conditions, lifecycle cost, and project standards.
Protection, Measurement, and Communication
Protection and measurement equipment should be specified together with the primary switchgear.
For CTs, typical parameters include:
- ratio;
- accuracy class;
- burden;
- short-time thermal withstand;
- dynamic withstand.
For VTs, the main parameters include ratio, accuracy class, and burden.
Protection relays may provide overcurrent, earth-fault, voltage, transformer, or motor protection. Relay requirements may refer to the IEC 60255 series.

The protection system should provide suitable selectivity, operating speed, and reliability, so that a fault can be isolated without unnecessarily disconnecting healthy parts of the system.
Modern MV switchgear may also support IEC 61850, Modbus, SCADA, remote I/O, and digital metering, depending on project requirements.
Interlocking and Operating Safety
Mechanical and electrical interlocks help prevent unsafe operations.
Typical interlocking functions include preventing:
- unintended circuit-breaker operation;
- operation of a disconnector under load where not permitted;
- closing an earthing switch onto an energized circuit;
- energizing a circuit while the earthing switch is closed;
- access to an energized high-voltage compartment.
The exact arrangement depends on the switchgear design and operating sequence.
Internal Arc, LSC, and Partition Class
Internal Arc Classification
Where internal-arc protection is required, Internal Arc Classification (IAC) should be specified.
Common accessibility types include:
- IAC A— access restricted to authorized personnel;
- IAC B— unrestricted accessibility.
Tested sides may be identified as:
- F— front;
- L— lateral;
- R— rear.
For example:
IAC A FLR
means authorized-personnel accessibility with the front, sides, and rear included in the internal-arc classification.
IAC should always be considered together with the switchgear room, pressure-relief system, exhaust path, cable trench, clearances, and access arrangement.
Loss of Service Continuity
IEC 62271-200 uses LSC classifications to describe how much of the switchgear can remain energized when an accessible high-voltage compartment is opened.
The principal categories are:
- LSC1
- LSC2
- LSC2A
- LSC2B
Higher service-continuity requirements may allow more of the system to remain energized during maintenance, but the required LSC category should be selected according to the actual maintenance and operating philosophy.
Partition Class
IEC 62271-200 also distinguishes:
PM — metallic partitions or shutters separate accessible compartments from energized high-voltage parts.
PI — one or more partitions or shutters use insulating material.
LSC, partition class, and IAC describe different aspects of switchgear design and should be specified separately.
Installation Environment and Protection
Environmental conditions can affect insulation, temperature rise, enclosure design, and equipment life.
Important information includes:
- ambient temperature;
- altitude;
- humidity;
- dust and pollution;
- corrosive atmosphere;
- indoor or outdoor installation;
- seismic requirements.
Common enclosure protection levels may include IP2X, IP3X, IP4X, or IP54, depending on the application.
Corrosive environments may also require consideration of ISO 12944 C1–C5 atmospheric corrosion categories.
High altitude and high ambient temperature can require insulation correction or thermal derating.
For seismic projects, standards such as IEC 62271-207 or IEEE 693 may apply depending on the market.
Applicable Standards
MV switchgear projects commonly refer to the IEC 62271 series.
| Standard | Main Scope |
| IEC 62271-1 | Common requirements |
| IEC 62271-100 | AC circuit breakers |
| IEC 62271-102 | Disconnectors and earthing switches |
| IEC 62271-103 | Load-break switches |
| IEC 62271-105 | Switch-fuse combinations |
| IEC 62271-200 | AC metal-enclosed switchgear up to and including 52 kV |
| IEC 62271-201 | Solid-insulation enclosed switchgear |
| IEC 62271-202 | Prefabricated substations |
| IEC 62271-203 | Gas-insulated metal-enclosed switchgear above 52 kV |
| IEC 62271-207 | Seismic qualification |
The latest effective edition required by the project, utility, or country should always be confirmed before final design.
North American projects may instead use the IEEE C37.20 series and other ANSI/IEEE standards.
IEC and IEEE/ANSI systems may use different voltage classes, insulation levels, current ratings, and short-circuit rating conventions, so the final selection should follow the project location and utility requirements.
Information Required for an MV Switchgear Enquiry
A single-line diagram (SLD) is one of the most important documents for technical selection because it shows the relationship between incoming feeders, bus sections, transformers, outgoing feeders, and protection devices. This was already one of the strongest practical points in your original article.
For an accurate proposal, the following information should ideally be provided:
| Item | Required Information |
| System / rated voltage | Nominal and required switchgear voltage |
| Frequency | 50 Hz, 60 Hz, or project requirement |
| Rated current | Incoming and outgoing currents |
| Busbar current | Main and branch busbar ratings |
| Short-circuit breaking current | Circuit-breaker capability |
| Short-time withstand | kA and duration |
| Peak withstand current | Required peak value |
| Insulation level | Power-frequency and lightning-impulse withstand |
| Switching device | Circuit breaker or load-break switch |
| Protection | Relay functions and philosophy |
| CT / VT | Ratio, accuracy class, burden |
| LSC / partition class | Required category |
| IAC | Accessibility, sides, current and duration |
| IP degree | Required enclosure protection |
| Interlocking | Required operating interlocks |
| Cable / bus connection | Entry direction, cable size, bus duct, etc. |
| Environment | Temperature, altitude, humidity, dust, corrosion |
| Standards | IEC, IEEE/ANSI, local utility requirements |
| Communication | IEC 61850, Modbus, SCADA, etc. |
A request such as:
“We need 12 kV switchgear.”
is normally not enough for accurate configuration.
A more useful description would be:
“We need a 12 kV, 1250 A switchgear lineup with a 25 kA/3 s short-time withstand rating, including one incoming breaker, one metering unit, one bus section, and three transformer feeders according to the attached SLD.”
The final arrangement should still be confirmed against the SLD and technical specification.
CMC Electric Medium-Voltage Switchgear Solutions
CMC Electric provides medium-voltage switchgear solutions for power distribution applications.
Switchgear selection and quotation can be reviewed according to the customer’s SLD, rated voltage, rated current, short-circuit level, protection requirements, installation environment, and applicable standards.
Conclusion
Selecting the right medium-voltage switchgear requires coordinated consideration of voltage, insulation, current, short-circuit capability, switching devices, protection, service continuity, internal-arc performance, and site conditions.
A clear single-line diagram and complete technical specification are therefore the best starting point for accurate switchgear selection and quotation.